Cornelius 500-Series Service Manual Page 34

  • Download
  • Add to my manuals
  • Print
  • Page
    / 35
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 33
29 TD 184
Trouble RemedyProbable Cause
9. Unit goes off on
reset (contd)
Strips loose or
missing on
inside of
evaporator shell
Inspect and replace
evaporator shell if
necessary
Low ambient
temperature in
room where
unit is located
Maintain
temperature above
50 degrees
Gearmotor
sticking which
causes it to
draw excessive
amperage
Check amp draw of
gearmotor with an
amprobe
Plugged
capillary tube or
expansion
valve, causing
low back
pressure
Check back
pressure, replace
cap tube or valve,
evacuate and
re-charge system,
replace
drier-strainer
Slight leak,
causing low
back pressure
Check back
pressure, find gas
leak, repair leak,
evacuate system,
add drier and
recharge
Loose
hold-down assy
Check and tighten
or replace
Auger worn
excessively on
the inside
surfaces
causing thicker
flaked ice to be
made
Replace auger
Page view 33